Brand Name : kimoems or OEM
Model Number : RM33-180kVA
Certification : CE
Place of Origin : China
MOQ : 1PC
Payment Terms : ,T/T
Delivery Time : 10 work days
Power Range : 180kVA or 300kVA 420kVA 600kVA
Power Modules : 3pcs or 5pcs or 7pcs 10pcs
Power Module Rated Capacity : 60kw
Operation : 3P/3P,Online double conversion
Applications : Government, Finance, IT, Education, Transportation, Broadcasting, Medical, Energy, Etc.
Characteristics : Fully digital control, flexible and robust. 10 inch touch LCD, with loT functions. High reliability and environment adaptability, with protection of components level. Extreme high power density, 30kW in 2U, friendly for space and maintenance. Option of 30A
APlus Modular UPS (60kW Module) 180kVA 300kVA 420kVA 600kVA
Model | A+30U-180 (PM-60) | A+42U-300 (PM-60) | A+42U-420 (PM-60) | A+42U-600 (PM-60) |
Phase | 3-phase Input/3-phase Output | |||
Cabinet Capacity* | 180kW | 300kW | 420kW | 600kW |
Battery Type | External Battery | |||
Power Module Capacity | 60kVA/60kW | |||
Max Power Modules | 3 | 5 | 7 | 10 |
Wiring (Rear) | Top Entry | Top/Bottom Entry | Top/Bottom Entry | Top/Bottom Entry |
Switch Quantity | 3 | 2 | ||
INPUT | ||||
Rated Voltage | 3×380/400/415VAC (3PH+N) | |||
Voltage Range | 110-300VAC @50% load,176-276VAC @100% load | |||
Nominal Frequency | 50/60Hz (Auto Detection) | |||
Frequency Range | 40-70Hz | |||
Power Factor | >0.99 @100% load,>0.98 @50% load | |||
THDI | <3% @100% load | |||
OUTPUT | ||||
Rated Voltage | 3×380/400/415VAC (3PH+N) | |||
Voltage Regulation (Static) | ≤±1% typical (balanced load),≤±2% typical (unbalanced load) | |||
Nominal Frequency | 50/60Hz | 50/60Hz | 50/60Hz | 50/60Hz |
Frequency Range (Sync) | 46-54Hz or 56-64Hz | |||
Overload Capacity | ≤110%: 60min;111-125%: 10min;126-150%: 1min;>150%: 200ms | |||
THD | ≤2% (linear load);<4% (non-linear load) | |||
Efficiency | 96% | |||
Battery/Charging | ||||
Rated Voltage | ±192V-±240V (Selectable) | |||
Max Voltage | ±240V (12V×40 cells) | |||
Min Voltage | ±192V (12V×32 cells) | |||
Float Charge Voltage | 2.28V/cell (2.25-2.33V selectable) | |||
Equalize Voltage | 2.35V/cell | |||
Temp. Compensation | Supported | |||
Max Charging Current (per module) | 16A (Adjustable) | |||
Physical Specifications | ||||
Cabinet Dimensions (D×W×H, mm) | 1100×600×1475 | 1100×600×2010 | 1065×1000×2000 | |
Net Weight (kg) | 224 | 297 | 308 | 420 |
Operating Environment | ||||
Operating Temperature | 0-40°C | |||
Relative Humidity | 0-95% (non-condensing) | |||
Altitude* | Rated power <1000m | |||
IP Rating | IP20 | |||
Control & Management | ||||
RS-232/USB | Windows series, Linux, Mac | |||
SNMP (Optional) | SNMP card and browser power management | |||
Safety Standards | ||||
Safety | IEC/EN 62040-1 | |||
EMC | IEC/EN 62040-2 Category C3 | |||
Note: If the UPS is installed or used at an altitude above 1000m, the output power must be reduced by 1% per 100m. | ||||
Model | Description | Dimensions (D×W×H, mm) | Weight (kg) | |
PM-60 | 3-in/3-out 60kVA/60kW Power Module | 750×438×130 (3U) | 44 |
![]() |